HVAC Rebates

Rebate amounts for new heating and cooling equipment replacing existing equipment or as part of a retrofit project.

Packaged Terminal Air Conditioning and Heat Pumps

Measure Rebate
Any Size $50.0

Must have an EER rating of greater than: 12.8 - (.213 x (BTUH / 1000))

Back to Top

Unitary and Split System Air Conditioning

Measure  Rebate Min. Efficiency
< 65,000 BTUH  $200.00/unit 14.0 SEER
65,000 — 135,000 BTUH  $40.00/ton 11.0 EER
136,000 — 240,000 BTUH  $40.00/ton 10.8 EER
241,000 — 760,000 BTUH  $40.00/ton 10.0 EER
> 760,000 BTUH  $40.00/ton 9.7 EER
Back to Top

Air Source Heat Pumps

Measure Rebate Min. Efficiency
Cooling Heating
< 65,000 BTUH (split) $400.00/unit 14.0 SEER 7.7 HSPF
< 65,000 BTUH (single pkg) $400.00/unit 14.0 SEER 7.7 HSPF
65,000 — 135,000 BTUH $40.00/ton 11.0 EER 2.2 COP
136,000 — 240,000 BTUH $40.00/ton 10.8 EER 2.0 COP
> 240 ,000 BTUH $40.00/ton 10.0 EER 2.0 COP
Back to Top

Water Source Heat Pumps

Measure Rebate Min. Efficiency
< 240,000 BTUH @ 85°F $40.00/ton 14.0 EER
Back to Top

Ground Water Source Heat Pumps (Open Loop)

Measure Rebate Min. Efficiency
Cooling Heating
< 135,000 BTUH @ 59°F Entering Water $80.00/ton 16.2 EER 3.6 COP
Back to Top

Ground Coupled Heat Pumps (Closed Loop)

Measure Rebate Min. Efficiency
Cooling Heating
< 135,000 BTUH @ 77°F Entering Water $60.00/ton 14.1 EER 3.1 COP
Back to Top

Air Cooled Chillers

Measure Rebate Min. Efficiency
Any Size $40.00/ton 9.56 EER full load
10.41 EER IPLV
  • The chiller efficiency rating must be based on ASHRAE 90.1-2007 chiller efficiency standards.
  • A manufacturer’s specification sheet with the rated EER must accompany the application.
  • The design performance EER must meet or exceed the minimum efficiencies listed above.
Back to Top

Water Cooled Chillers

Measure Rebate Min. Efficiency
< 150 ton $40.00/ton 0.79 KW/ton full load
0.68 KW/ton part load
150 — 300 ton $40.00/ton 0.72 KW/ton full load
0.63 KW/ton part load
> 300 ton $40.00/ton 0.64 KW/ton full load
0.57 KW/ton part load
  • The chiller efficiency rating must be based on ASHRAE 90.1-2007 chiller efficiency standards.
  • A manufacturer’s specification sheet with the rated KW/ton full load and IPLV must accompany the application.
  • The design performance KW/ton full load and IPLV must meet or exceed the minimum efficiencies listed above.
Back to Top

Heat Pump Water Heaters

Measure Rebate Min. Efficiency
< 80 gallon tank $1,000.00 3.0 COP
80 — 150 gallon tank $2,000.00 3.0 COP
> 150 gallon tank $2,500.00 3.0 CO
Back to Top

Thermal Storage

Measure Rebate
Thermal Storage Unit $100.00/KW shifted
Back to Top

Other

Measure Rebate Min. Efficiency
Variable frequency drives up to 250 HP $40.00/hp  
Outside air economizer using two enthalpy sensors $250.00  
Energy recovery ventilation (ERV) with a minimum of 450 CFM and as part of an electric-powered system $1.00/CFM ARI 1060 rating > 65% winter effectiveness
HVAC occupancy sensor $30.00  
Window Film $2.00/sq ft Solar heat gain coeffient of 0.40 or less
  • VFDs are for use with supply fans, return fans, exhaust fans, water pumps and cooling tower pumps only
  • Air economizers must be installed on CEE Tier 1 or higher efficiency units
  • Window Film rebates are applicable for windows facing East, West and South (North-facing windows do not qualify). Installation must result in energy savings on a cooling system powered by electricity.
Back to Top